CVE-2019-7275· optergy / enterprise· CWE-601
Optergy Proton/Enterprise Building Management System - Open Redirect
mediumseverity
6.1CVSS score
9%likelihood of exploitation, next 30 days
95%of all CVEs are less likely
Readycheck to confirm it
Optergy Proton/Enterprise Building Management System contains an open redirect vulnerability. An attacker can redirect a user to a malicious site and possibly obtain sensitive information, modify data, and/or execute unauthorized operations.
Impact
An attacker can exploit this vulnerability to redirect users to malicious websites, leading to phishing attacks or the download of malware.
Fix
Apply the latest security patches or updates provided by Optergy to fix the open redirect vulnerability.
How to confirm it
Send: GET {{BaseURL}}/updating.jsp?url=https://interact.sh/
Positive when: matches in header /(?m)^(?:Location\s*?:\s*?)(?:https?://|//)?(?:[a-zA-Z0-9\-_\.@]*)interact\.sh.*$/Run it with nuclei: nuclei -id CVE-2019-7275 -u <target>. This check is not marked as verified by its authors.
The full check
id: CVE-2019-7275
info:
name: Optergy Proton/Enterprise Building Management System - Open Redirect
author: 0x_Akoko
severity: medium
description: Optergy Proton/Enterprise Building Management System contains an open redirect vulnerability. An attacker can redirect a user to a malicious site and possibly obtain sensitive information, modify data, and/or execute unauthorized operations.
impact: |
An attacker can exploit this vulnerability to redirect users to malicious websites, leading to phishing attacks or the download of malware.
remediation: |
Apply the latest security patches or updates provided by Optergy to fix the open redirect vulnerability.
reference:
- https://packetstormsecurity.com/files/155268/Optergy-Proton-Enterprise-BMS-2.3.0a-Open-Redirect.html
- https://applied-risk.com/resources/ar-2019-008
- https://cxsecurity.com/issue/WLB-2019110074
- https://applied-risk.com/labs/advisories
- https://nvd.nist.gov/vuln/detail/CVE-2019-7275
classification:
cvss-metrics: CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N
cvss-score: 6.1
cve-id: CVE-2019-7275
cwe-id: CWE-601
epss-score: 0.09047
epss-percentile: 0.95324
cpe: cpe:2.3:a:optergy:enterprise:*:*:*:*:*:*:*:*
metadata:
max-request: 1
vendor: optergy
product: enterprise
tags: cve,cve2019,redirect,packetstorm,optergy,vuln
http:
- method: GET
path:
- "{{BaseURL}}/updating.jsp?url=https://interact.sh/"
matchers:
- type: regex
part: header
regex:
- '(?m)^(?:Location\s*?:\s*?)(?:https?://|//)?(?:[a-zA-Z0-9\-_\.@]*)interact\.sh.*$'References
- https://packetstormsecurity.com/files/155268/Optergy-Proton-Enterprise-BMS-2.3.0a-Open-Redirect.html
- https://applied-risk.com/resources/ar-2019-008
- https://cxsecurity.com/issue/WLB-2019110074
- https://applied-risk.com/labs/advisories
- https://nvd.nist.gov/vuln/detail/CVE-2019-7275
Use this check only on systems you are authorised to test. Where the data comes from